Technical informations
| Range: | ComPact |
|---|---|
| Range of product: | ComPact NS1600b...3200ComPact NS630b...1600 |
| Product name: | Micrologic |
| Product or component type: | Trip unit |
| Trip unit name: | Micrologic 5.0 |
| Trip unit technology: | Electronic |
| Range compatibility: | ComPact NS1600b...3200ComPact NS630b...1600 |
| Device application: | Distribution |
| Poles description: | 4P3P |
| Protected poles description: | 3t3t + N/24t |
| Trip unit protection functions: | Selective protection |
| Protection type: | for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection |
| [In] rated current: | 630 A at 50 °C800 A at 50 °C1000 A at 50 °C1250 A at 50 °C1600 A at 50 °C2000 A at 50 °C2500 A at 50 °C3200 A at 50 °C |
| Network type: | AC |
| Network frequency: | 50/60 Hz |
| Mounting mode: | DrawoutFixed |
| Long time pick-up adjustment type Ir: | Adjustable 9 settings |
|---|---|
| Long time pick-up adjustment range: | 0.4...1 x In |
| Long time delay adjustment type: | Adjustable 9 settings |
| [tr] long-time delay adjustment range: | 0.7...16.6 s at 7.2 x Ir0.5...24 s at 6 x Ir12.5...600 s at 1.5 x Ir |
| Thermal memory: | 20 mn |
| Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
| [Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
| Short-time delay adjustment type: | Adjustable |
| [tsd] short-time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
| Instantaneous pick-up adjustment type Ii: | Adjustable 9 settings |
| Instantaneous pick-up adjustment range: | 2...15 x InOff |
| Earth-leakage protection: | Without |
| Zone selective interlocking ZSI: | Without |
| Local signalling: | 3 LEDs (red) for electrical fault1 LED (red) for internal error |