Technical informations
| Range of product: | ComPacT NSX100...250 new generation |
|---|---|
| Product or component type: | Trip unit |
| Poles description: | 4P |
| Protected poles description: | 4D |
| Neutral position: | Left |
| Network type: | AC |
| Network frequency: | 50/60 Hz |
| Trip unit name: | Micrologic 6.2 A |
| Trip unit technology: | Electronic |
| Trip unit protection functions: | LSIG |
| Trip unit rating: | 160 A at 40 °C |
| Protection type: | Overload (long time)Short time short-circuit protectionInstantaneous short-circuit protection |
| Mounting mode: | Fixed |
|---|---|
| [Ue] rated operational voltage: | 690 V AC 50/60 Hz |
| Neutral protection setting: | No protection0.5 x Ir1 x Ir |
| Long time pick-up adjustment type Ir: | Adjustable 9 settings |
| Long time pick-up adjustment range: | 63...160 A |
| Long time delay adjustment type: | Adjustable |
| [tr] long-time delay adjustment range: | 15...400 s 1.5 x Ir0.5...16 s 6 x Ir0.35...11 s 7.2 x Ir |
| Thermal memory: | 20 minutes before and after tripping |
| Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
| [Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
| Short-time delay adjustment type: | Adjustable |
| [tsd] short-time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
| Instantaneous pick-up adjustment type Ii: | Adjustable |
| Instantaneous pick-up adjustment range: | 1.5...15 x In, accuracy: +/- 15 % |
| Ground-fault time delay adjustment type -tg: | Adjustable |
| Ground-fault pick-up adjustment type: | Adjustable |
| [tg] ground-fault time delay adjustment range: | 0...0.4 s I²t=off0.1...0.4 s I²t=on |
| [Ig] ground-fault pick-up adjustment range: | 0.2...1 x In (In > 40 A), accuracy: +/- 10 %0.4...1 x In (In = 40 A), accuracy: +/- 10 %Ig enable on/off |
| Zone selective interlocking ZSI: | With |
| Communication of data: | Demand current and powerInstantaneous and demand valuesMaintenance indicatorsEarth leakage current |
| Display type: | LCD display |
| Type of measurement: | Ammeter |
| Electrical data recording: | Maintenance indicators |
| Compatibility code: | NSX160 |
| Communication port protocol: | Modbus |