calcActive())">
SCHNEIDER
TeSys GV7 - circuit breaker - 3P - AC-3 - 60...100 A - thermal-magnetic - GV7RS100
GV7RS100
Obsolete product, here is the list of products that can replace the reference GV7RS100 :GV4PE115S GV4PE115N
Technical informations
| Range: | TeSys |
|---|---|
| Range of product: | TeSys GV7 |
| Product name: | TeSys GV7 |
| Product or component type: | Circuit breaker |
| Device short name: | GV7R |
| Device application: | Motor |
| Poles description: | 3P |
| Network type: | AC |
| Utilisation category: | AC-3 conforming to IEC 60947-4-1 |
| Network frequency: | 50/60 Hz conforming to IEC 60947-4-1 |
| Breaking capacity: | 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-265 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-270 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity: | 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2100 % at 220/240 V AC 50/60 Hz conforming to IEC 60947-2100 % at 380/415 V AC 50/60 Hz conforming to IEC 60947-2100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit rating: | 60...100 A |
| Trip unit technology: | Thermal-magnetic |
| Mounting mode: | By screwsBy clips |
|---|---|
| Mounting support: | Kit for fixing the switchgearRailFlushPanel mounting |
| Mounting position: | Vertical |
| Motor power kW: | 45 kW at 400...415 V AC 50/60 Hz75 kW at 660...690 V AC 50/60 Hz |
| Control type: | Rocker lever |
| [In] rated current: | 100 A |
| [Ue] rated operational voltage: | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage: | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ith] conventional free air thermal current: | 100 A conforming to IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage: | IEC 60947-2 8 kV |
| Power dissipation: | 5 W |
| Power dissipation per pole: | 5 W |
| Mechanical durability: | 50000 cycles |
| Electrical durability: | 30000 cycles for AC-3 at 440 V In50000 cycles for AC-3 at 440 V In/2 |
| Maximum operating rate: | 25 cyc/h |
| Rated duty: | Continuous conforming to IEC 60947-4-1 |
| Connection pitch: | 35 mm without spreaders45 mm with spreaders |
| Connections - terminals: | BarsCable with lug - external diameter: 10 mmScrewBare cable connectors 1.5...95 mm² |
| Tightening torque: | 10 N.m on screw M6 screw type 15 N.m on bare cable connectors for cable 1.5...95 mm² |
| Mechanical robustness: | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27Vibrations: 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6 |
| Suitability for isolation: | Yes conforming to IEC 60947-1 |
| Phase failure sensitivity: | Yes conforming to IEC 60947-4-1 § 7-2-1-5-2 |
| Height: | 161 mm |
| Width: | 105 mm |
| Depth: | 111 mm |
| Product weight: | 2.04 kg |
| Compatibility code: | GV7RS |
In short
Reference
GV7RS100
Product Name
TeSys GV7 - circuit breaker - 3P - AC-3 - 60...100 A - thermal-magnetic - GV7RS100
Range
TeSys
Device function
Moteur
Related Categories