calcActive())">
SCHNEIDER
circuit breaker VigiComPact NSX400F, 36 kA at 415 VAC, MicroLogic 2.3 trip unit 400 A, add-on Vigi MB module, 3P 3d - LV432731
LV432731
Obsolete product, here is the proposed substitution for the reference LV432731 : C40F34V400
Technical informations
| Range: | ComPact |
|---|---|
| Product name: | ComPact NSX |
| Range of product: | ComPact NSX400...630 |
| Device short name: | VigiCompact NSX400F |
| Product or component type: | Circuit breaker with Vigi add-on |
| Device application: | Distribution |
| Poles description: | 3P |
| Protected poles description: | 3t |
| [In] rated current: | 400 A at 40 °C |
| [Ue] rated operational voltage: | 440 V AC 50/60 Hz |
| Network type: | AC |
| Network frequency: | 50/60 Hz |
| Suitability for isolation: | Yes conforming to EN/IEC 60947-2 |
| Utilisation category: | Category A |
| Breaking capacity: | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-285 kA at 240 V AC 50/60 Hz conforming to UL 50825 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-236 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-210 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-235 kA at 480 V AC 50/60 Hz conforming to UL 50820 kA at 600 V AC 50/60 Hz conforming to UL 50820 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-230 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code: | F 36 kA 415 V AC |
| Trip unit name: | Micrologic 2.3 |
| Trip unit technology: | Electronic |
| Trip unit protection functions: | LSoI |
| Control type: | Toggle |
| Mounting mode: | Fixed |
| [Ui] rated insulation voltage: | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage: | 8 kV |
| [Ics] rated service breaking capacity: | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-236 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-210 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-210 kA at 525 V AC 50/60 Hz conforming to IEC 60947-225 kA at 500 V AC 50/60 Hz conforming to IEC 60947-230 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability: | 15000 cycles |
| Electrical durability: | 3000 cycles at 690 V In6000 cycles at 690 V In/26000 cycles at 440 V In12000 cycles at 440 V In/2 |
| Mounting support: | Backplate |
| Upside connection: | Front |
| Downside connection: | Front |
| Connection pitch: | 45 mm |
| Protection type: | L |
| Trip unit rating: | 400 A at 40 °C |
| Long time pick-up adjustment type Ir: | Adjustable 9 settings |
| Long time pick-up adjustment range: | 160...400 A |
| Long time delay adjustment type: | Fixed |
| [tr] long-time delay adjustment range: | 16 s at 6 x Ir |
| Thermal memory: | 20 minutes before and after tripping |
| Short-time pick-up adjustment type Isd: | Adjustable 9 settings |
| [Isd] short-time pick-up adjustment range: | 1.5...10 x Ir |
| Short-time delay adjustment type: | Fixed |
| Instantaneous pick-up adjustment type Ii: | Fixed |
| Instantaneous pick-up adjustment range: | 4800 A |
| Earth-leakage protection: | With |
| Earth-leakage add-on module name: | MB |
| Earth-leakage protection class: | Class A |
| Residual earth-leakage sensitity adjustment type: | Fixed |
| [I?n] residual earth-leakage sensitive adjustment: | 0.3 A |
| Residual earth-leakage time delay adjustment type: | Adjustable 4 settings |
| Zone selective interlocking ZSI: | Without |
| Number of slots: | 7 slot(s) |
| Local signalling: | Flashing LED (green) for ready to operateLED 105 % Ir (red) for overloadLED 90 % Ir (orange) for overload |
| Width: | 135 mm |
| Height: | 355 mm |
| Depth: | 110 mm |
| Product weight: | 6.05 kg |
| Compatibility code: | NSX400 |
In short
Reference
LV432731
Product Name
circuit breaker VigiComPact NSX400F, 36 kA at 415 VAC, MicroLogic 2.3 trip unit 400 A, add-on Vigi MB module, 3P 3d - LV432731
Range
Compact
Device function
Distribution
Related Categories