The cross-sectional area of a cable depends on several factors.
Domestic Use
For Standard (Domestic) Use
Consider the current rating of the power outlets being used: 16 (e.g., Odace S520058), 20, or 32 amps.
For Domestic Applications
Determine the minimum cable cross-section, the number of outlets per circuit breaker, and the maximum rating as specified in NFC15-100 (the standard governing electrical installations)(1). These values do not account for voltage drops (see article 525 of NF C 15-100). For larger cross-sections, refer to the general rules of NF C 15-100 and more specifically to C15-105.
Other Applications
The elements for determining the appropriate cable should be considered in this order:
The First Element: Determine the Outlet to be Installed
To do this, you will need:
- The maximum power consumption of the device to be connected
- The type of network (alternating or direct current) and voltage values
- The number of connectors: number of phases, neutral, and earth connections
- The protection rating of the outlet
The protection rating takes into account the environment where the device will be located, considering exposure to dust and liquids.
Example: I need an outlet for a 28 Amp 3-phase compressor with a phase-to-phase voltage of 400V and a neutral connection; I am installing it in an open shelter. The outlet will therefore need a higher rating: 32A 5-pole with IP44 protection (IP rating as indicated in C15-103), specifically reference PKF32F435 with a PKZ100 base. The associated circuit breaker for protection will be a 32A 4-pole circuit breaker (or 3P+N). For guidance on choosing a circuit breaker, see the paragraph on circuit breaker selection.
The Second Element: Type of Cable to be Installed
Consider:
- Multi-conductor or single-conductor cable
- Rigid or flexible construction
- Type of conductor: copper or aluminum
- Type of insulation
Depending on the type of cable to be installed, the cable characteristics will vary, and its current-carrying capacity will differ accordingly.
The Third Factor: Installation Method
The cable will generate different amounts of heat depending on whether it is installed in a conduit or bundled with several other cables.
With these first three elements, we can pre-determine the appropriate cable cross-section.
The Final Factor: Connection Distance
For devices other than lighting, the voltage drop must not exceed certain limits (for example, in a "yellow tariff" installation, or "monitored tariff" in most cases, the voltage drop must not exceed 3% for lighting and 5% for other applications).
When the voltage drop exceeds acceptable limits, the cross-section predetermined using elements a/b/c must be increased so that the voltage drop falls within the maximum allowable values.One-Elec provides expert guidance on selecting the appropriate electrical wires and cables for your power outlet installations.